SCM5B35

Linearized 4-Wire RTD Input Modules

SCM5B35 Photo
SCM5B35 Photo

In RTD temperature measurement applications requiring a very high level of accuracy, the SCM5B35 4-Wire RTD input module offers a significant advantage over 3-wire measurement techniques. The SCM5B35 measures only the voltage dropped across the RTD and almost completely ignores the resistance or length of the RTD lead wires. The SCM5B34 3-Wire RTD module provides lead resistance compensation, but requires equal lead resistances, while the SCM5B35 does not require matched lead resistances. Each SCM5B35 RTD input module provides a single channel of RTD input which is filtered, isolated, amplified, linearized, and converted to a high-level analog voltage output. This voltage output is logic switch controlled, which allows these modules to share a common analog bus without the requirement of external multiplexers. The SCM5B modules are designed with a completely isolated computer side circuit which can be floated to ±50V from Power Common, pin 16. This complete isolation means that no connection is required between I/O Common and Power Common for proper operation of the output switch. If desired, the output switch can be turned on continuously by simply connecting pin 22, the Read-Enable pin, to I/O Common, pin 19. RTD excitation is provided from the module by a precision current source. The excitation current is available on two leads which are separate from the two input signal measuring leads. The excitation current does not flow in the input signal leads, which allows RTD measurement to be totally independent of lead resistance. The excitation current is very small (0.25mA for 100 Ohm Pt and 120 Ohm Ni and 1.0 mA for 10 Ohm Cu) which minimizes self-heating of the RTD. Signal filtering is accomplished with a six-pole filter which provides 95dB of normal-mode rejection at 60Hz and 90dB at 50Hz. Two poles of this filter are on the field side of the isolation barrier, and the other four are on the computer side. After the initial field-side filtering, the input signal is chopped by a proprietary chopper circuit.

Isolation is provided by transformer coupling, again using a proprietary technique to suppress transmission of common mode spikes or surges. The module is powered from +5VDC, ±5%. A special input circuit on the SCM5B35 modules provides protection against accidental connection of power-line voltages up to 240VAC.

Figure SCM5B35

Figure SCM5B35



Product profile:
SCM5B35 Isolated 4 Wire RTD Input Amplifier Signal Conditioning Module 5B35

ModuleInput RangeDescriptionPDF
SCM5B35-01 -100°C to +100°C (-148°F to +212°F) 5B35 Linearized 4-Wire RTD Isolated Input Amplifier Modules See PDF
SCM5B35-02 0°C to +100°C (+32°F to +212°F) 5B35 Linearized 4-Wire RTD Isolated Input Amplifier Modules See PDF
SCM5B35-03 0°C to +200°C (+32°F to +392°F) 5B35 Linearized 4-Wire RTD Isolated Input Amplifier Modules See PDF
SCM5B35-04 0°C to +600°C (+32°F to +1112°F) 5B35 Linearized 4-Wire RTD Isolated Input Amplifier Modules See PDF
SCM5B35-05 -100°C to +200°C (-148°F t o +392°F) 5B35 Linearized 4-Wire RTD Isolated Input Amplifier Modules See PDF
SCM5B35C-01 0°C to +120°C (+32°F to +248°F) 5B35 Linearized 4-Wire RTD Isolated Input Amplifier Modules See PDF
SCM5B35C-02 0°C to +120°C (+32°F to +248°F) 5B35 Linearized 4-Wire RTD Isolated Input Amplifier Modules See PDF
SCM5B35C-03 0°C to +160°C (+32°F to +320°F) 5B35 Linearized 4-Wire RTD Isolated Input Amplifier Modules See PDF
SCM5B35N-01 0°C to +300°C (+32°F to +572°F) 5B35 Linearized 4-Wire RTD Isolated Input Amplifier Modules See PDF

Features

top
  • Interfaces to 100 Ohm Platinum, 10 Ohm Copper, or
  • True 4-Wire Input
  • Linearizes RTD Signal
  • High-Level Voltage Output
  • 1500Vrms Transformer Isolation
  • ANSI/IEEE C37.90.1 Transient Protection
  • Input Protected to 240VAC Continuous
  • 160dB CMR
  • 95dB NMR at 60Hz, 90dB at 50Hz
  • CSA Certified, FM Approved, CE and ATEX Compliant
  • Mix and Match SCM5B Types on Backpanel